
How to reduce installation problems
and
improve reliability of UL 2161 transformers
Ventex Generation III UL 2161 LISTED electronic power supplies
are different.
With the growing number of electronic power supplies being used in the sign industry
and adoption of the UL2161 standard, sign builders will encounter some new situations.
The following are guidelines to make the features and installation of Ventex
VT series power supplies easier to understand. Using this information and following
these suggestions during installation will help eliminate possible long or short-term
problems.
What is UL 2161?
UL 2161 is a standard created by UL to address the change in
the 1996 National Electric Code. This standard requires electronic
power supplies, with secondary
output greater than
2000V to ground, to have secondary ground fault protection. This is now a requirement
in UL 48.
How does this affect an electronic power supply?
Previously, if electronic power supplies had secondary ground fault protection,
the “trip point” was 25-35 mA to ground. To be UL 2161 LISTED,
that “trip point” is now a maximum of 15 mA to ground. This “reduced
trip point”, along with capacitance coupling, could make all electronic
neon power supplies seem more sensitive than products that you have used
in the past.
What is capacitance coupling?
Capacitance Coupling results from the electric field that surrounds every AC
current carrying conductor, such as GTO cable or neon tubes. It has the ability
to conduct AC current through air between the tubes, GTO, electronic power
supply and any mounting surface. This can rob current (mA) from the tubes
resulting in a loss of brightness, cause over loading of the power supply
or result in false tripping. These effects increase with the voltage increases.
If you have ever seen an unpowered tube glow while sitting next
to tubes or GTO powered by an electronic transformer, that is
an example of capacitance coupling. Stray capacitive current
from the lit circuit is exciting the non-energized tube. Another
example includes the dimming or tripping of a lit tube when you
grasp it with your hand. When this happens, you are actually
drawing current from power supply by capacitance coupling.
All signs have an “effective” ground plane. This
could be the “can” of a channel letter or the wall,
window or even Plexiglas that exposed neon tubes are mounted
on. These ground planes are in effect electrical conductors.
Any high voltage wiring, as well as neon tubes in the sign will
have capacitance coupling to ground. In extreme cases this can
cause neon power supplies with GFI to “trip” due
to excess ground fault current or over loading.
What effects can Capacitance Coupling
have on electronic transformers?
• Over Loading - Some electric power supplies
on the market can deliver currents or voltages in excess of the
rated values when loaded with stray capacitance. This will result
in over-heating and can cause premature failure of the unit.
Ventex’s VT series incorporates a unique design which controls
the current to prevent this.
• Electronic Cross Talk can occur between power supplies, tubes,
or GTO leads in multi-transformer applications. If the tubes
or GTO leads on different power supplies are close, you may have
a sign that will not light unless the power supplies are turned
on in a specific order. If the power supplies are placed too
close together, power supply overheating or overloading can occur.
• False Tripping is a major problem caused by excessive capacitance
coupling. Ventex VT series power supplies have patented circuitry
to help eliminate most false tripping. How can I minimize the
effects of capacitance coupling? Maximize the distance between
tubes, GTO leads, cans, ground planes, etc. Ventex recommends
the GTO wire and glass tubes be 1.5” from any surface or
ground plane. While this is not always possible or practical,
any separation is better than direct contact with any surface.
GTO Sleeving will increase the GTO electrical insulation, but
will not reduce capacitance coupling. In fact, it may even increase
it. A key thought to remember which will help; Always treat the
GTO wires with the same respect you treat the neon tubes!
Ventex Generation III Neon Power Supplies.
All Ventex units starting approximately June, 2002 incorporate
the latest Generation III technology to make these units the
most user friendly available. This new technology provides the
following.
1. Brown-Out Protection: Eliminates false trip shut down due
to low input voltage. At extreme low voltages, the unit may not
light the neon tube but will re-strike when the voltage recovers.
2. Surge Protection: Internally clamps input voltage spikes
to prevent damage to the neon power supply (this is available
on Outdoor CL units only)
3. “Triple Shot” Starting: Automatically will attempt
to start or restart up to three times for intermittent problems
to resist spurious false trips. You will see up to three “flashes” of
light at the home-run electrodes when this occurs.
Wiring Suggestions for Ventex VT Series Power Supplies
1. Do Not run GTO leads from any electronic power supply in
metallic conduit. If this is done, you will experience severe
loss of driving distance and brightness, suffer GTO failure and
possible false tripping.
2. Do Not load Ventex VT series power supplies with a mA meter
or use a primary side dimmer. The VT series maintains 30 ma
output regardless of load or primary voltage.
3. Do Not over load. The VT Series has protection and will “trip” if
there is an over load of glass and/or excessive capacitance coupling.
4. Keep GTO leads, particularly “Home Run” wires
as short and as far from each other and all surfaces as possible.
Ventex recommends 1.5 inches as a minimum if possible.
5. If a high voltage GTO cable has to be run through a thin
sheet metal wall, special care must be taken. The sharp edge
of a hole
could cause rapid deterioration of the GTO cable. This can
eventually cause a ground fault condition and “tripping”. Use
the largest diameter hole possible and always use an approved
bushing to center the cable in the hole.
6. If long jumper leads must be used, place these as close
to the middle of the glass run as possible. The voltage and
capacitive
current will be lower closer to the middle of the sign, which
will lessen the chance of over loading or tripping.
7. If leads have to cross, try to space them as far apart
as possible and cross them at right angles.
8. Maintain as much space as possible between multiple power
supplies, their tubes and wiring. This will minimize the
effects of “electronic cross talk.”
9. Balance glass load and “homeruns” as much as possible.
This will minimize the chance of tripping.
10. In all signs it is best to wire from the “inside out”.
This minimizes current loss due to capacitance coupling through
the GTO and the chance of over loading and “tripping”.
11. Dedicated Primary Circuits (Outdoor Application) Ground
Fault Protected Units (UL 2161 Listed) require a dedicated circuit
for proper operation. NEC Section 600.5(A) disallows any other “draw” or “load” attached
to either the sign circuit or neutral. What this means is that
all wiring must be in accordance with NEC and UL 48 which requires
a dedicated circuit without shared neutrals. Lack of a clean
ground & neutral or fluctuating voltage may cause nuisance
tripping
Examples of Wiring
Wiring a multiple lamp sign with a border. |

GOOD |

POSSIBLE TRIPPING |
| More Examples of Wiring |
 |
 |
 |
GOOD
Short “homerun” leads
Balanced load |
ACCEPTABLE
Long “homerun” leads
Balanced load |
BAD
Unbalanced power unit lead
Unbalanced capacitive load
Possible GFI tripping |
|
| Architectural or Cove Lighting can present
problems with current loss and ground fault tripping if long
or unbalanced homeruns are used. |
| BAD |
 |
ACCEPTABLE
May be dim |
 |
| GOOD - BRIGHT |
 |
Note: The long jumper wires in the above installation must
be kept away from all surfaces. If this is not done one of
two problems could occur. The jumper could cause tripping
by allowing one tube to start before the other by means of
its capacity to ground. This long jumper will result in a
GFI trip. |
Special Considerations for Wiring Channel Letter Units
Odd stroke channel letters can present wiring problems. It will
not be always possible to minimize the GTO cable length from
the power unit. An example of a single stroke “V” is
shown below with different methods of wiring. For best performance,
the leads must be supported away from the “can”.
 |
 |
 |
ACCEPTABLE
Balanced lead lengths
Balanced capacitive load |
GOOD
Short lead lengths
Balanced capacitive load |
BAD
Unbalanced lead lengths
Unbalanced capacitive load
Possible GFI tripping |
Multiple Letters on One VT Series CL Unit
Note:
1. You will probably decrease the driving distance due to the
proximity of metal and wiring. In extreme cases, driving distance
can be decreased by more than 20%.
2. You may increase the possibility of false tripping due to
unbalanced capacitance coupling to the various metal parts.
3. Always support the GTO in the receiving area from the metal
with standoffs, etc.
Capacitance Coupling and Distance
NOTE: Distance is the Best Way to reduce Capacitance Coupling
and loss.

In the above illustration GTO Cable is shown in three different
locations
in an aluminum “can”.
A. The GTO is on the bottom of the “can” in a corner.
This situation causes maximum current loss. A loss of 1 mA per
foot of GTO or more can occur depending on voltage and application.
B. Current loss has been reduced by 70% by moving GTO cable
0.5 of an inch from the corner.
C. Current loss from “A” has been reduced by 91%
by moving the GTO cable 1.25 inches away from the corner and
surfaces of the “can”.
The Effect of Temperature on the Power Supply
Increasing temperature in Electronic Neon Power Supplies and
Electromechanical transformers will reduce life. An increase
in temperature of 10°C (18°C) will result in a reduction
of life expectancy of about 50%. To ensure long life, any power
supply mounted inside an enclosure must be adequately ventilated.
Ventex VT series indoor power supplies have an operating temperature
rating of 32° to 104°F(0° to 40°C). Outdoor
CL models have a rating of–30° to 122°F (-34° to
50°C.) If the operating temperature cannot be maintained
within these limits, then de-rate the driving distances as
in the chart below.

Rev. 7 – © October 2002 Ventex Technology, Inc.
 |
Click button
to go back
to page top |
 |
Click button to download
a PDF copy of this Application Guide
(Requires Adobe Acrobat Reader) |
 |
Click button to download
a FREE copy of Adobe
Acrobat Reader |
|